Add to Cart
12/24/36kV Medium Voltage Transformer Bushing Metallic Coating Touch Proof MV/LV/HV Epoxy Resin Casting Single Phase
1.Product Introduction:
Voltage transformer is fully enclosed cast insulation structure, the primary and secondary winding, the toroidal core are all encapsulated in the epoxy resin casting body to improve the
filterability and moisture resistance. The product plug part is designed to conform to the 2 # inner cone (EN 50181). The overall structure is designed to be fully shielded surface. It is used indoor for measuring voltage, electric energy and protective relaying in single-phase or three-phase AC circuit with the frequency 50Hz or 60Hz and highest voltage for equipment 36kV.
Technical Data
1. Installation site: Indoor
2. Rated frequency: 50/60Hz
3. Load power factor: coso=0.8 (lagging)
4. Technical standard accords with: IEC 60044-2
IEC 61869-183
Item | Specification | Unit | Data |
1 | Um | kV | Up to 36 |
2 | Rated Insulation Level | kV | Up to 36/70/170 |
3 | Rated Primary Voltage | V | 33000/√3 22000/√3 11000/√3 |
4 | Rated Secondary Voltage | V | 110/√3 or 110/3 |
Type | Rated primary voltage (kV) | Rated secondary voltage (kV) | Accuracy classes combination | Rated output (VA) | Thermal limiting current (VA) | Rated insulation level(kV) |
JDZX13-12/24/36PC | 33/√3 22/√3 11/√3 | 0.11//√3 | 0.2 | 20 | 300 |
12/28/75 24/50/125 36/70/170 |
0.5 | 50 | |||||
1 | 80 | |||||
0.11/√3/0.11/3 | 0.2/6P(3P) | 150 | ||||
25/50 | ||||||
0.5/6P(3P) | 50/50 |
Remarks: Upon request we are glad to offer transformers according to other standards or with non-standard technical specs.
Outline drawing
We are specializing in MV&LV Current Transformer Voltage Transformer, and Cable Accessories with great quality and competitive price. Really hope to be a business partner of your company.