Add to Cart
Separable Connector 200 A 15 kV Elbow Arrester Surge Arrester for panel
Application
Chuangyin® Elbow Arrester is widely applicable for connecting underground XPLE cable to packaged substation, RMU, cable branch box, buried transformer and leads of other HV equipments equipped with loadbreak bushings, junctions, or connectors in 200 A power network. Combines metal oxide varistor module in a rubber elbow to provide overvoltage system protection.
The interface complys with IEEE standard 386, 8.3/14.4 kV, and 15.2/26.3 kV 200 A loadbreak design.
Features
Made of high quality EPDM rubber and metal oxide
Fully shielded and insulated
Protecting electrical components against over-voltage and transients
The connected braid to manage short circuit currents
100% factory tested
In compliance with IEC 60099.4-2006, JB/T 8952
Construction
1. Insulating Layer
2. Conducting Shield
3. MOV Module
4. Arrester Cap
5. Grounding Wire
Technical Data
Item | YH5WZ-17/45 | YH5WS-17/50 |
System Nominal Voltage (kV) | 15 | 15 |
Max. Voltage Class (Um) (kV) | 17 | 17 |
Max. Continuous Operating Voltage (kV) | 13.6 | 13.6 |
Voltage of DC 1mA Current (kV) | ≥24 | ≥25 |
Lightning Impulse Residual Voltage (kV) | ≤45.0 | ≤50.0 |
Steep Current Residual Voltage (kV) | ≤51.8 | ≤57.5 |
Switching Impulse Residual Voltage (kV) | ≤35 | ≤42.5 |
Long Duration Current Impulse Withstand (A) | 150 | 100 |
High Current Impulse Withstand (kA) | 65 | 65 |
5min EPDM Insulation Housing Withstand (kV) | 39 | 39 |
Kit Contents
Elbow Arrester
Wipers
Silicone Grease
Grounding Wire
Installation Instruction
Certificate
Ordering Instructions
Product | Part Number |
15 kV,200 A Elbow Arrester (Distribution) | CYS-ASZT—YH5WS-17/50 |
15 kV,200 A Elbow Arrester (Sub-station) | CYS-ASZT—YH5WZ-17/45 |