Add to Cart
Indoor Plug-in type Connector 35KV En50180-50181 Suitable For GIS
Plug-in Termination Kits is suitable for GIS incoming and outgoing wire connection. It is designed to mate with epoxy insulated bushing, and connect wire to switchgear fully shielded, fully insulated, fully sealed. Your technician can install, repair or maintain equipment and power cable system without
undermining seal between bushing and GIS.
Meets the standard of EN50180-50181 interface type 2#, 3#.
Parameters:
Part Number | 2# | 3# |
Voltage Rating | 35KV | 35KV |
Rated Current | 800A | 1250A |
AC Witnstand Voltage 5Min | 117KV | 117KV |
DC Withstand Voltage15 Min | 104KV | 104KV |
PD At Ambient Temperature | 45KV10pC | 45KV10pC |
Impulse Voltage At Elevated Temperature | 200KV | 200KV |
Cable Section | 50-240mm | 50-630mm |
Structure
1.Epoxy Insulated Bushing
2.Iocking halves
3.stress relief cone
4.Plug-in termination kit
5.Protection cover
6.pressure spring
7.Cable sheath
8.Grounding wire
9.Cable
Cable not included
Packing
Termination housing
locking halves
Protection cover
Cable sheath
Braided ground wire
CFS
Wipers
Installation instruction
silicone grease
Certificate