36kv MV Indoor Current Transformer Epoxy Resin Casting Single Phase Delta Transformer

Ask Latest Price
Brand Name :Chuangyin
Model Number :LZZBJ10-36
Certification :Kema,CE,SGS,TUV
Place of Origin :Shenzhen
MOQ :1set
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :36,000,00pcs per year
Packaging Details :Plywood
Price :Negotiable
Rated insulation level :36/70/170kv
Installation site :Indoor
Usage :Measuring and Protection
Standard :IEC60044-1
Material :Electromagnetic
Working Environment :-30~70℃ Humid≤85%,indoor
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description


36kv Indoor MV Current Transformer Current Transformer Epoxy Resin Casting ​



1. Product Introduction:

LZZBJ10-36 current transformer, epoxy resin casting insulation and fully enclosed support construction, encloses primary & secondary windings and annular core in the epoxy resin casting body. The product has the large periphery insulation creepage distance, withoutstanding dirtiness and dampness. Be suitable for measuring electric capacity, and protective relaying in the power system of 36kv

2. Technical Data:



Main technical parameter

  1. Rated insulation voltage: 36/70/170kV
  2. Rated frequency: 50/60hz
  3. Installation Site: Indoo
  4. Standards: IEC60044-1(IEC61869-1&2)

3. Specification:

Rated

transformation ratio(A)

Accuary classes combination

(VA)

Rated output

(ALF) (FS) Short-time thermal current Ith(kA/S) Rated dynamic current Idyn(kA)

Measuring

Protective

0.2(S) 0.5 10P

15/5

……

200/5

0.2(S)/0.2(S)

0.2(S)/0.5

0.5/0.5

0.2(S)/10P

0.5/10P

10 15

10

15

10

5

(10)

100I1n 250I1n
300/5 25 63
400/5 31.5 80
500/5 40 100
600/5 40 100
800/5 63 130
1000/5 63 130
1500/5 80 160

Two Secondary Double Ratio

Rated

transformation ratio(A)

Accuary classes combination

(VA)

Rated output

(ALF)

(FS) Short-time thermal current Ith(kA/S) Rated dynamic current Idyn(kA)

Measuring

Protective

0.2(S) 0.5 10P

15-30/5

20-40/5

……

200-400/5

0.2(S)/0.2(S)

0.2(S)/0.5

0.5/0.5

0.2(S)/10P

0.5/10P

10 15

10

15

10

5

(10)

75I1n 187.5I1n
300-600/5 31.5 80
500-1000/5 40 100
600-1200/5 50 130
750-1500/5 80 160
4. Outline Drawing:
36kv MV Indoor Current Transformer Epoxy Resin Casting Single Phase Delta Transformer
5.Photos:
36kv MV Indoor Current Transformer Epoxy Resin Casting Single Phase Delta Transformer