Add to Cart
Clamp-on Rogowski Coil Current Transformer Red/Black Flexible Power Meters
General data:
.Ambient operating temp:-20……+70℃
.Ambient storage temp.:-25……+75℃
.Standard Safety:IEC 61010-1:2001,600V CATⅢ
Specification: unit :mm
Dimensions | CY-RCT01-80 CY-RCTA01-80 |
Window A | 80 |
Coil DB B | 93.5 |
Coil Length C | 300 |
Output connection | UL2586-ESB2*24AWG L=150cm(as required) Coax terminated with safety male BNC connector L =300cm(as required) UL2586-esb2*24AWG L=150cm(as required)with integrator |
Electrial Parameter:
Type Data | CY-RCT01-80 | CY-RCTA01-80 | |
Current Range | 10A-10KA | 10A-6000A | |
Frequency | 25Hz-20kHz | 45Hz-600Hz | |
Output Voltage | Rated curent | 1000A | 1000A,1500A,2000A,2500A |
50Hz | 100mv AC | 333mV | |
1mV/A | |||
Max output | / | 3.0V AC max | |
Accuracy | <1%@25ºC(45-65Hz) | <1%@25ºC(45-65Hz) | |
Phase error | <60@25ºC(45-65Hz) | <60@25ºC(45-65Hz) | |
Output sensitivity | ±2%Max (No Calibration) | 1% | |
±0.5%@25ºC(with Calibration | |||
Linearity error | ±0.2%(10%-100%IIn) | ±0.2% | |
Position Sensitivity | ±0.2% | ±2% | |
External Influence | ±0.2% Max | ±1.5%Max | |
Power Supply | / | 10-30VDC,30m A MAX. |
Remarks:
Upon request we are glad to offer transformers according to other standards or with non-standard technical specs.
The quality is assurance, the reasonable price, welcome to order, ordering or the proxy.
Kindly Note:
Our Factory Products Catalog as Follow:
I. Instrument Transformer(Epoxy Resin Type, upto72.5kV)
i. LV & MV Current/Voltage Transformer
ii. Electronic Instrument Transformer/LPIT/Sensor Split Core Current Transformer/Rogowski Coil
iii. Split Core Current Transformer/Rogowski Coil
Usage Instruction: