Shenzhen Chuangyin Co., Ltd.

Shenzhen Chuangyin Co., Ltd. We are manufacturer. We will take high-quality service and high-quality products to satisfy you. We have advanced management experience, production flow and quality

Manufacturer from China
Verified Supplier
7 Years
Home / Products / MV Current Transformer /

12kV MV Voltage Transformer Single Phase 50 / 60Hz For Measuring / Protective

Contact Now
Shenzhen Chuangyin Co., Ltd.
Visit Website
City:shenzhen
Province/State:guangdong
Country/Region:china
Contact Person:MrDieky Lin
Contact Now

12kV MV Voltage Transformer Single Phase 50 / 60Hz For Measuring / Protective

Ask Latest Price
Brand Name :Chuangyin
Model Number :JDZXW5-12
Certification :KEMA/type test report
Place of Origin :China
MOQ :1-100PCS
Price :Negotiable
Payment Terms :L/C, T/T
Supply Ability :36000PCS/YEAR
Delivery Time :5-10 workdays
Packaging Details :Plywood
Insulation Type :Dry type/Epoxy cast
Installation :Outdoor
Voltage :12kV
Rated Frequency :50Hz/60Hz
Standard :IEC/GB
Rated frequency :50Hz or 60Hz
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Chuangyin Voltage Transformer-JDZXW5-12

Description:

Epoxy resin casting and full-closed construction, single-pole for phase to ground connection, It is widely used for measuring voltage, electric energy and protective relaying in the sing-phase or three phase power system with the frequency 50Hz or 60Hz and highest voltage for equipment 12kV

Basic technical data:

1. Installation: outdoor

2. Insulation type: dry, epoxy cast

3. Highest voltage for equipment Um (r.m.s.) 12kV

4. Rated power-frequency withstand (induced) voltage (r.m.s.): 28kV

5. Rated lightning impulse withstand voltage (peak): 75kV

5. Rated frequency: 50Hz or 60Hz

6. Applied standard: IEC 61869-1&3 (IEC 60044-2)

Shenzhen Chuangyin Co., Ltd has three manufacturing bases ,they are Jiangxi Chuangyin Co.,Ltd, Zhuhai Chuangyin Co.,Ltd and Joint-Venture Adex-Chuangyin Electric Co.,Ltd(Bangladesh); with 40,000 square meters of modern standard workshop and a number of first-class production line and test equipments, by many years’ experience for three dedicated engineering teams, the annual output of medium &low current transformer and voltage transformer is more than 36000 sets and CT, relay is more than 25 million pcs.

Specification:

Rated Primary Voltage(kV) Rated Secondary Voltage(V) Accuracy classes combination Rated Burden (VA) Thermal limiting Output (VA)

Rated Insulation Level

(kV)

Measuring Protective

10/√3

11/√3

100/√3

110/√3

100/3

110/3

0.2 10 300 12/28/75
0.5 25
1 50
0.2/3P 10/50 200
0.5/3P 25/50

Inquiry Cart 0