Add to Cart
Chuangyin Voltage Transformer-JDZW1-17.5,24
Description:
Epoxy resin casting and full-closed construction, Double-pole for phase-phase connection, It is widely used for measuring voltage, electric energy and auxiliary power in the sing-phase or three phase power system with the frequency 50Hz or 60Hz and highest voltage for equipment 36kV
Basic technical data:
1. Installation: Outdoor
2. Insulation type: Dry, Epoxy cast
3. Highest voltage for equipment Um (r.m.s.):17.5kV, 24kV
4. Rated power-frequency withstand voltage (r.m.s.):38kV, 50kV
5. Rated lightning impulse withstand voltage (peak):95kV, 125kV
5. Rated frequency: 50Hz / 60Hz
6. Applied standard: IEC 61869-1 &3 (IEC 60044-2)
Specification:
Rated Primary Voltage (kV) | Rated Secondary Voltage (V) | Accuracy classes combination | Rated Burden (VA) | Thermal limiting Output (VA) | Rated Insulation Level (kV) | |
13.8 20 22 24 | 100 110 115 120 | 220 240 | 0.2 | 25 | 300 500 | 17.5/38/95 24/50/125 |
0.5 | 50 | |||||
1 | 100 | |||||
3 | 200 | |||||
5 | 500 |